Panic hardware, also known as an exit device or fire exit hardware when used on fire doors, is designed to provide fast and easy egress to allow building occupants to exit safely in an emergency. Code publications define panic hardware as, “a door-latching assembly incorporating a device that releases the latch upon the application of a force in the direction of egress travel.”
Determining whether the egress doors of a facility need panic hardware can be a challenge, even for the experts. While most jurisdictions have adopted the International Building Code (IBC) requirements, it’s important to be aware that there are also areas like New York City where state or local requirements vary and will need to be consulted in order to ensure code compliance.
According to all editions of the IBC starting with the 2006 edition, panic hardware is required for doors serving three use groups:
1. Assembly occupancies with an occupant load of 50 people or more
2. Educational occupancies with an occupant load of 50 people or more
3. High hazard occupancies with any occupant load
Note that these requirements only apply to doors that lock or latch. They do not apply if a door has push/pull hardware and no lock or latch.
In facilities that are required to follow NFPA 101 – Life Safety Code, there are four occupancy classifications where panic hardware is required:
1. Assembly occupancies with an occupant load of 100 people or more
2. Educational occupancies with an occupant load of 100 people or more
3. Day care occupancies with an occupant load of 100 people or more
4. High hazard occupancies with an occupant load of more than 5 people
Be aware that if a room contains electrical equipment, NFPA 70 – National Electrical Code may require panic hardware to be installed. This requirement was first included in the 2002 edition of the NEC, and has been modified in subsequent editions. Beginning with the 2014 edition, doors that latch or lock, within 25 feet of the required work area, serving the following rooms, require listed panic hardware or fire exit hardware:
1. Where equipment is 800 amps or more and contains overcurrent devices, switching devices, or control devices
2. Where equipment is 600 volts or more
Residential, business and mercantile occupancies such as apartments, office buildings or retail facilities typically would not require panic hardware on any doors unless there is an assembly, educational, or high hazard area within the building with an occupant load of 50 or more (per the IBC) or 100 or more (per NFPA 101). If these buildings contain electrical rooms that meet the criteria above, panic hardware would be required on those rooms.
Current codes require panic hardware to be mounted between 34 inches and 48 inches above the floor. Existing panic hardware may have been installed at other mounting locations in accordance with previous code requirements.
No additional locking device (deadlock, chain, padlock and hasp, etc.) may be installed on a door required to have panic hardware, and panic hardware may not be equipped with any device that prevents the release of the latch when the touch-pad or cross-bar is pressed. The exception to this is a delayed egress or controlled egress device allowed by code in certain applications.
Of course, panic hardware can always be installed for convenience, security, or durability, even if it is not required by code. The AHJ may also request panic hardware in other instances if he or she believes that a hazard exists which warrants a need for panic hardware in order to provide life safety.
Lori Greene, DAHC/CDC, CCPR, FDAI, FDHI is the Manager of Codes and Resources for Allegion. For more information about this topic and to download a free reference guide on codes, visit iDigHardware.com/guide.
Next Read next on FacilitiesNet Commercial Boilers Recalled Due to Burn Hazard The recalled boilers pose a burn hazard due to a delayed ignition or flame rollout. Broken Record: OSHA Fines Dollar General Over Workplace Safety OSHA inspected stores in Florida and Georgia and catalogued many of the same violations Dollar General has refused to correct at its stores throughout the nation.One Worker Dead, Three Injured in Manhattan Construction Accident A wall collapse on a building being demolished caused the worker’s death.ICC Releases Building Security Report and Guidance Report offer guidance on building risk assessments, building safety administration, hardening facilities and tactical considerations.
The recalled boilers pose a burn hazard due to a delayed ignition or flame rollout.
OSHA inspected stores in Florida and Georgia and catalogued many of the same violations Dollar General has refused to correct at its stores throughout the nation.
A wall collapse on a building being demolished caused the worker’s death.
keyless door lock for panic bar Report offer guidance on building risk assessments, building safety administration, hardening facilities and tactical considerations.